Design and characterization of a system for loss factor measurement in MV underground cable joints under temperature variation conditions.
[Laurea magistrale], Università di Bologna, Corso di Studio in
Ingegneria dell'energia elettrica [LM-DM270]
Documenti full-text disponibili:
|
Documento PDF (Thesis)
Disponibile con Licenza: Salvo eventuali più ampie autorizzazioni dell'autore, la tesi può essere liberamente consultata e può essere effettuato il salvataggio e la stampa di una copia per fini strettamente personali di studio, di ricerca e di insegnamento, con espresso divieto di qualunque utilizzo direttamente o indirettamente commerciale. Ogni altro diritto sul materiale è riservato
Download (6MB)
|
Abstract
Cable joints are considered to be the weakest components of the MV cable network, being the ones with the highest failure rate. Furthermore, from statistical analysis of different cable network failure data, a noticeably increase in cable joint breakdowns has been showed during summer months. The request for Distribution System Operators to avoid line outages as much as possible indicates a significant need for non-invasive diagnostic technologies able to monitor the health condition of MV cable junctions. Moreover, a better knowledge is required on the main causes of the detected increase in cable joint failure rate, in which temperature seems to play an important role. The present master thesis consists in the design and complete characterization of a simple and cheap laboratory setup for loss factor measurements on cable joints. Using the developed circuit, tan delta measurements are performed on four thermally cycled cable joint samples and the trend in relation to temperature variations has been investigated and widely discussed. In particular, it has been found that the loss factor of cable joint samples decreases considerably when temperature rises and vice-versa. From result analysis, some hypotheses have been made trying to explain this particular behavior of the loss factor versus temperature. In particular, temperature variations seem to cause expansions and contractions of the different dielectric layers present in cable joint, giving rise to pressure fluctuations at the interface between them. Consequently, variations in the breakdown strength of the joint insulation system and in the amount of conduction losses are expected to happen. These conclusions must be demonstrated by future studies and tests on cable junctions. It is worth saying that a conference proceeding has been published from the present work, and, currently, a journal paper is submitted, waiting to be approved.
Abstract
Cable joints are considered to be the weakest components of the MV cable network, being the ones with the highest failure rate. Furthermore, from statistical analysis of different cable network failure data, a noticeably increase in cable joint breakdowns has been showed during summer months. The request for Distribution System Operators to avoid line outages as much as possible indicates a significant need for non-invasive diagnostic technologies able to monitor the health condition of MV cable junctions. Moreover, a better knowledge is required on the main causes of the detected increase in cable joint failure rate, in which temperature seems to play an important role. The present master thesis consists in the design and complete characterization of a simple and cheap laboratory setup for loss factor measurements on cable joints. Using the developed circuit, tan delta measurements are performed on four thermally cycled cable joint samples and the trend in relation to temperature variations has been investigated and widely discussed. In particular, it has been found that the loss factor of cable joint samples decreases considerably when temperature rises and vice-versa. From result analysis, some hypotheses have been made trying to explain this particular behavior of the loss factor versus temperature. In particular, temperature variations seem to cause expansions and contractions of the different dielectric layers present in cable joint, giving rise to pressure fluctuations at the interface between them. Consequently, variations in the breakdown strength of the joint insulation system and in the amount of conduction losses are expected to happen. These conclusions must be demonstrated by future studies and tests on cable junctions. It is worth saying that a conference proceeding has been published from the present work, and, currently, a journal paper is submitted, waiting to be approved.
Tipologia del documento
Tesi di laurea
(Laurea magistrale)
Autore della tesi
Lama, Filippo
Relatore della tesi
Correlatore della tesi
Scuola
Corso di studio
Indirizzo
Electrical Engineering
Ordinamento Cds
DM270
Parole chiave
Tan Delta,Cable Joint,Measurement Setup,Temperature cycles,Loss Factor,Circuit Charachterization,Resistive Divider,Interfacial Discharges,LabVIEW Program,Cable Fault
Data di discussione della Tesi
20 Dicembre 2018
URI
Altri metadati
Tipologia del documento
Tesi di laurea
(NON SPECIFICATO)
Autore della tesi
Lama, Filippo
Relatore della tesi
Correlatore della tesi
Scuola
Corso di studio
Indirizzo
Electrical Engineering
Ordinamento Cds
DM270
Parole chiave
Tan Delta,Cable Joint,Measurement Setup,Temperature cycles,Loss Factor,Circuit Charachterization,Resistive Divider,Interfacial Discharges,LabVIEW Program,Cable Fault
Data di discussione della Tesi
20 Dicembre 2018
URI
Statistica sui download
Gestione del documento: